Low Voltage Distribution Network Design, Load Flow, and Short Circuit Analysis

Overview

This project demonstrates the end-to-end workflow of designing and analyzing a 1000 kVA, 415 V low-voltage distribution network. The network was modeled in AutoCAD for single-line diagrams, feeder pillar layouts, protection schemes, and cable sizing, and validated through ETAP simulations. Both load flow and short circuit analyses were performed to ensure the system meets voltage regulation, reliability, and safety standards.

Tools & Technologies

  • AutoCAD – Single-line diagrams, feeder pillar design, voltage drop calculations, and cable sizing
  • ETAP – Load flow analysis, voltage profile verification, transformer loading, system loss evaluation, and short circuit analysis

Key Features

  • Designed a 1000 kVA package unit (11 kV / 0.415 kV transformer) with 8 feeders and 20+ loads
  • Verified voltage drop ≤ 4% across all feeders through AutoCAD calculations
  • Performed ETAP load flow analysis confirming:
    • Bus voltages ≥ 96%
    • Transformer loading at 60.5% of rated capacity
    • System losses < 3% of total load
  • Conducted short circuit analysis to calculate fault levels at each bus and evaluate fault current waveforms for breaker and relay coordination
  • Optimized protection scheme with 630 A fuses, 200 A circuit breakers, and CTs (100/5 A)
  • Enhanced network reliability, reducing outage risk by >25%

Repository Contents

  • /AutoCAD_Files – Single-line diagrams, feeder pillar schematics, and cable schedules
  • /ETAP_Files – Load flow and short circuit models with simulation results
  • /Reports – Design documentation, results, and analysis summaries

How to Use

  1. Open AutoCAD files (.dwg) to review the single-line diagram and feeder pillar design.
  2. Load ETAP project files to run load flow and short circuit simulations.
  3. Compare AutoCAD design calculations (voltage drops, cable sizes) with ETAP simulation results for validation.

Results

  • Load Flow Analysis: Stable bus voltages, safe transformer utilization, and controlled system losses
  • Short Circuit Analysis: Fault levels verified at all buses, with peak fault currents reaching ~65–70 kA near the transformer
  • Protection Coordination: Correct breaker and relay sizing ensured safe isolation under fault conditions
  • System Reliability: Improved resilience and reduced outage risk

Contact

Created by Raein Layegh Pour
LinkedIn | Portfolio


If you found this project useful, please consider giving it a star on GitHub!

About

Low Voltage Distribution Network Design, Load Flow, and Short Circuit Analysis using AutoCAD and ETAP

Topics

Resources

Stars

Watchers

Forks

Releases

No releases published

Packages

 
 
 

Contributors