Role-Based Access Control for Secure SunSpec Modbus

In 2025, the SunSpec Alliance created a working group to define a secure version of the protocol based on Modbus TCP/Security from modbus.org. The protocol used mTLS with an X.509v3 certificate that included a role extention. To provide granual authorization to SunSpec Modbus holding registers, the SunSpec Server extracts the role in the certificate to grant point-level read and write access to different users based on the role they are assuming.

Roles-to-Rights Maps

Point-by-point read/write access is in the /rbac directory and summarized in roles_to_rights.md.

Roles

SunSpec has defined the following roles with these general permissions:

  • ReadOnlySunSpec - Read access to all data. No write permissions. This role may be used by DER owners for monitoring production data or DER vendors for monitoring, diagnostics, and/or prognostics.
  • GridServiceSunSpec - Read access to all data. Write access to commanded and autonomous functions. No access to networking or protection functions.
  • NetworkAdministratorSunSpec - Read access to all data. Write access to SunSpec network holding registers.
  • SuperAdministratorSunSpec - Full read/write access to all SunSpec points. This role may be used by (a) the grid operator, (b) the system installer, (c) the DER vendor for repairs, or (d) a DER owner in situations where they are operating a microgrid.

Optionally, the device vendor may add additional roles. For example, IEC 62351-8 includes a set of additional roles:

  • VIEWER
  • OPERATOR
  • ENGINEER
  • INSTALLER
  • SECADM: Security administrator
  • SECAUD: Security auditor
  • RBACMNT: RBAC management

Rights

Permissions in the case of SunSpec RBAC are limited to read and write access of the Modbus holding registers. IEC 62351-8 goes further and includes rights for dataset management and manipulation, reporting, file reads and writes, file management, object control, object configuration, creating/editing/deleting settings groups, and adjusting server or service security settings. However, in the context of SunSpec Modbus, this functionality is not provided by the application protocol.

Note: all roles must have the ability to read the ID and L points for all models in order for the SunSpec discovery process to work.

Standards Harmonization

There were two primary references used in the creation of the Secure SunSpec standard: "MODBUS/TCP Security" from modbus.org and IEC 62351-8 "Role-based access control for power system management". The Secure SunSpec Specification deviated from these reference documents in several ways, including the approach to authorization, as described below.